Page 343 - Demo
P. 343
343SWITCHGEAR & DISTRIBUTIONFusesConsumer Unit Fuse-LinksPart No. Current Rating BS 1361 Colour CodingPrincipal Dimensions(A) BS 1361 (A) BS 88 L (mm) L (ins) D (mm) D (ins)LA2 - 2 - 23 7/8 6.35 1/4LA5 5 - White 23 7/8 6.35 1/4LC2 - 2 - 26 1 10.32 13/32LC5 - 5 - 26 1 10.32 13/32LC8 - 8 - 26 1 10.32 13/32LC10 - 10 - 26 1 10.32 13/32LC15 15 16 Blue 26 1 10.32 13/32LC20 20 20 Yellow 26 1 10.32 13/32LD6 - 6 - 29 1 1/8 12.7 1/2LD10 - 10 - 29 1 1/8 12.7 1/2LD16 - 16 - 29 1 1/8 12.7 1/2LD20 - 20 - 29 1 1/8 12.7 1/2LD25 - 25 - 29 1 1/8 12.7 1/2LD30/32 30 32 Red 29 1 1/8 12.7 1/2LK35 - 35 - 35 1 3/4 16.67 1/32LK40 - 40 - 35 1 3/4 16.67 1/32LK45 - 45 Green 35 1 3/4 16.67 1/32%u2022 Lawson type L Fuse-Links are for use in household consumer units or other single phase installations with fault levels up to 16.SkA%u2022 They can be fitted into Pullcap Fuse-Holders or other suitable Fuse-Holders230/240 Consumer Unit Fuse-Links to IEC 60269-3/BS 88-3 and BS 1361Rated Voltage 240V a.c. Breaking Capacity 16.SkA a.c. Breaking Range and Utilisation Category gGNote: In addition to the current ratings specified in BS 1361, additional ratings certified to BS 88 have been included to meet other requirements.